The Breaker Load Calculator estimates current demand across circuits to select correct breaker ratings and maintain compliance with wiring regulations.
Report an issue
Spotted a wrong result, broken field, or typo? Tell us below and we’ll fix it fast.
About the Breaker Load Calculator
Breaker load is the current a circuit breaker must carry without tripping during normal operation. It also anticipates short-term surges and continuous duty. The calculator converts load power or current into a breaker rating and a minimum conductor ampacity, using common North American code guidance.
You can start with power in watts or kilowatts, or directly with current in amperes. The result applies the 125% rule for continuous loads, rounds up to a standard breaker size, and proposes a starting wire gauge. It then flags when temperature, power factor, or grouping of conductors may require further derating or different materials.
Use it during design, submittals, and field verification. It keeps units consistent and makes assumptions explicit, so teams can compare dimensions, materials, and ratings across drawings and product data sheets.

How to Use Breaker Load (Step by Step)
Begin by gathering basic electrical data for the circuit. You need system voltage, whether it is single-phase or three-phase, and the load’s power or running current. If the load is continuous—expected to run for three hours or more—mark it as continuous.
- Select system type: single-phase or three-phase.
- Enter nominal voltage in volts and load power in watts or kilowatts, or enter current directly.
- Set power factor if known; otherwise use 1.0 for resistive loads.
- Flag the load as continuous if it operates at least three hours at a time.
- Choose conductor material (copper or aluminum) and insulation rating for a wire size suggestion.
The calculator returns load current, the adjusted current for continuous duty, a recommended breaker size, and a preliminary wire gauge. Review any advisory notes, especially for temperature corrections and conductor bundling that affect ampacity.
Formulas for Breaker Load
These formulas convert between power and current and apply common sizing rules. Use consistent units and note whether the load is single-phase or three-phase.
- Single-phase running current: I = P / (V × PF), where I in amperes, P in watts, V in volts, PF is power factor (0–1).
- Three-phase running current: I = P / (√3 × V × PF) for P in watts and line-to-line voltage V.
- Continuous load adjustment: I_cont = 1.25 × I_run (125% of running current).
- Breaker rating: choose the next standard size ≥ I_req, where I_req is I_cont for continuous loads, else I_run.
- Minimum conductor ampacity (simplified): Ampacity ≥ I_cont for continuous loads; check temperature and bundling corrections.
- Optional voltage drop check (single-phase, approximate): V_drop ≈ 2 × I × R_per_length × length.
Most molded-case circuit breakers are 80% rated for continuous loading unless marked and listed for 100% operation. Always verify manufacturer data and applicable codes when selecting final ratings and materials.
Inputs, Assumptions & Parameters
The calculator focuses on common branch and feeder sizing. It uses the following inputs to estimate breaker and wire selections and to surface derating needs.
- Voltage (V) and system type (single- or three-phase).
- Load power (W or kW) or running current (A); provide one of these.
- Power factor (PF), default 1.0 if unknown.
- Load type: continuous or noncontinuous.
- Conductor material and insulation rating (e.g., copper, 75°C).
- Ambient temperature or conductor grouping if a derating check is needed.
Default ranges work for most building systems: 120–240 V single-phase and 208–600 V three-phase. For large motors, welders, medical equipment, or unusual duty cycles, article-specific rules may override these general methods. The tool flags values outside typical dimensions or units and suggests a deeper review.
Step-by-Step: Use the Breaker Load Calculator
Here’s a concise overview before we dive into the key points:
- Choose single-phase or three-phase to match the supply.
- Enter the nominal voltage and either load power or running current.
- Set the power factor or accept the default.
- Indicate whether the load is continuous (≥3 hours).
- Pick conductor material and insulation rating for a wire suggestion.
- Review calculated current, breaker size, and minimum ampacity.
These points provide quick orientation—use them alongside the full explanations in this page.
Example Scenarios
Residential lighting circuit: 120 V single-phase, 1,440 W of LED lighting, PF ≈ 1.0, continuous. Running current I = 1,440 / (120 × 1.0) = 12 A. Continuous adjustment: 1.25 × 12 = 15 A. The next standard breaker is 15 A. Copper 14 AWG at 60°C is commonly rated for 15 A; check local code for exact ampacity and materials. What this means: A 15 A breaker with 14 AWG copper is appropriate for this continuous lighting load.
Data room branch circuit: 208 V three-phase, 18 kW server/UPS load, PF = 0.95, continuous. I = 18,000 / (√3 × 208 × 0.95) ≈ 18,000 / 342.0 ≈ 52.6 A. Continuous adjustment: 1.25 × 52.6 ≈ 65.8 A. The next standard breaker is 70 A. Minimum conductor ampacity should meet ≥66 A before temperature and grouping corrections; 4 AWG copper (75°C) is a common starting point, subject to derating. What this means: Use a 70 A three-phase breaker and size conductors for at least 66 A, then validate derating.
Assumptions, Caveats & Edge Cases
The calculator uses simplified methods that align with common practice, but specific articles of electrical codes may change results. Always confirm final selections against project specifications and local requirements.
- Standard breakers are typically 80% rated for continuous loading unless listed for 100% operation.
- Motors, welders, HVAC units, and EVSE have article-specific sizing rules that can differ from general branch circuits.
- Conductor ampacity depends on material, insulation temperature rating, ambient temperature, and the number of current-carrying conductors.
- Available standard breaker sizes may force you to round up beyond the nearest theoretical value.
- Voltage drop can dictate larger conductors for long runs even when ampacity is adequate.
When edge cases appear—such as poor power factor, high inrush, or aluminum conductors in small dimensions—consult manufacturer data and the applicable code articles. Document assumptions so field teams and inspectors see how you reached each rating.
Units & Conversions
Consistent units prevent errors when moving between product sheets, drawings, and on-site measurements. Current is measured in A, voltage in V, and power in W or kW. Power factor (PF) is unitless. Conductor dimensions are often specified in American Wire Gauge (AWG) or square millimeters.
| From | To | Conversion |
|---|---|---|
| W | kW | kW = W ÷ 1000 |
| kW (single-phase) | A | A = (kW × 1000) ÷ (V × PF) |
| kW (three-phase) | A | A = (kW × 1000) ÷ (√3 × V × PF) |
| VA | kVA | kVA = VA ÷ 1000 |
| °C | °F | °F = (°C × 9 ÷ 5) + 32 |
Use these conversions before entering values and when checking outputs against datasheets. If your materials list shows kVA instead of kW, convert or set PF to 1.0 for an apparent power calculation.
Troubleshooting
If your results look too high or too low, check the basics first. Confirm voltage, system type, and whether power is real power (kW) or apparent power (kVA). Make sure power factor is reasonable for the equipment.
- Verify that the load is continuous or noncontinuous as defined.
- Ensure you are not mixing single-phase and three-phase formulas.
- Check that materials and insulation ratings match the wire table you use.
- Look for hidden derating: high ambient temperature or more than three current-carrying conductors.
If the recommended breaker is not a stocked size, round up to the next available rating and confirm conductor ampacity. When in doubt, review the manufacturer’s application notes for the specific breaker frame and wire insulation.
FAQ about Breaker Load Calculator
What is breaker load?
Breaker load is the current a circuit will draw under normal operation. It includes adjustments for continuous duty so the breaker does not trip during sustained use.
Why do I multiply continuous loads by 125%?
Many codes require sizing continuous loads at 125% to prevent nuisance trips and overheating. This ensures the breaker operates within its long-term thermal limits.
Does power factor change the breaker size?
Yes. For the same kW, a lower power factor increases current, which can increase the breaker and conductor size. Always use the manufacturer’s PF if available.
Can the calculator pick the final wire size?
It provides a starting gauge based on ampacity. You must verify temperature corrections, grouping, installation conditions, and local code before final selection.
Glossary for Breaker Load
Breaker rating
The nominal ampere value printed on a circuit breaker, indicating the maximum current it should carry continuously without tripping.
Continuous load
A load expected to run for three hours or more. It is sized at 125% for breakers and conductors unless otherwise permitted.
Noncontinuous load
A load that does not run for three hours or more. It is typically sized at 100% of running current.
Power factor
The ratio of real power to apparent power, between 0 and 1. Lower values mean higher current for the same kW.
Ampacity
The maximum current a conductor can carry continuously under specified conditions without exceeding its temperature rating.
Derating
Reducing allowable ampacity due to temperature, number of current-carrying conductors, or installation conditions.
Voltage drop
The reduction in voltage along a conductor due to resistance. Excessive drop can require larger conductors even if ampacity is adequate.
AWG
American Wire Gauge, a standardized system describing conductor size. Lower AWG numbers indicate larger cross-sectional dimensions.
References
Here’s a concise overview before we dive into the key points:
- NFPA 70: National Electrical Code (NEC) overview
- UL 489: Molded-Case Circuit Breakers standard
- Eaton: Applying Overcurrent Protective Devices guide
- Mike Holt: Understanding continuous and noncontinuous loads
- NEMA AB 1: Molded Case Circuit Breakers and Molded Case Switches
These points provide quick orientation—use them alongside the full explanations in this page.